Similiar to othe SmartOne devices, the unit is field programmable using the control panel keypad or Hand Held Programmer. The owner location message and reporting type can be customized by the use of a programming utility utilized with the control panel. A status LED is mounted on the unit and indicates the status by a 2 or 9 second flash interval. A Trouble condition inhibits the status LED completely.
While the Pull Station is designed for quick, efficient emergency response, its double action PUSH/PULL levers prevent accidental operation. The Pull Station can be mounted in an indoor or outdoor weatherproof backbox (Model SBG-32S or Model SGB-32C) or a North American 2-1/2 in. (64 mm) deep single gang box. The Station terminal block on the AI module accepts 14,16 and 18 AWG (1.5 mm2, 1.0 mm2, and 0.75 mm2) wire.Size #18 is the minimum requirement.
The Pull Station has a unique labeling method which provides the installer the greatest amount of flexibility with out the expense of having to carry extra inventory. Seven heavy duty Lexan® self adhesive labels are shipped with each station:
- Fire Alarm
- FM-200 Release
- CO2 Release
- FE-13 Release
- AF-36 Release
- HFC-227ea Release
- FK-5-1-12 Release
- Fire System Release
- THERMATIC Release
- NOVEC 1230 Release
Features Kidde® Addressable Manual Pull Stations Series 3300
- Exclusive KIDDE® Design
- Unique Field Labeling for either Fire Alarm or Suppression Applications
- Dual Action Operation
- Interfaces directly to Kidde Addressable Control Panel SLC Communication Loop
- FM Approved
- cULus Listed for US and Canada
- Other domestic approvals in process
- Surface and Weatherproof Backboxes
- Flashing LED
- Keylock for Rese
Technical Specification Kidde® Addressable Manual Pull Stations Series 3300
- Station Type: Double Action, with integral Smart-One Addressable Module
- Initiating Device Circuit: Style B (Class B) Wiring
- EOL Resistor Value: 10 K Ohm (06-129025-003)
- Max. Circuit Resistance: 50 Ohm (25 ohm per conductor)
- Max. Circuit Capacitance: 0.1μF
- Operating Temperature Range: -40ºF to 150ºF (-40ºC to 66ºC)
- Operating Humidity Range: 0-95% RH
- Construction: Die-cast metal housing
- Compatible Electrical Boxes: Indoor: Sheet metal Model SGB-32S, Outdoor: Weatherproof Die-cast Model SGB-32C
- Shipping Weight: 1.12 lbs. (510 g)
- Dimensions: 4-3/4 in. H x 3-1/4 in. W x 2-1/4 in. D
- Construction: Steel sheet metal.
- Conduit: Two knockouts for 1/2 in. conduit connectors, one on top and bottom.
- Mounting: Mounts to the box with (4) 8/32 screws, which ship with each box
Brochure & Datasheet Kidde® Addressable Manual Pull Stations Series 3300
Donwload Spesifikasi, Brosur dan Datasheet Kidde® Addressable Manual Pull Stations Series 3300 disini untuk mendapatkan informasi lebih jelas mengenai produk ini.
Harga Kidde® Addressable Manual Pull Stations Series 3300
Harga Kidde® Addressable Manual Pull Stations Series 3300 yang kami jual sangatlah bersaing. Silahkan langsung menghubungi kami di 081317698478, 087701989383 untuk mendapatkan harga Kidde® Addressable Manual Pull Stations Series 3300 terbaik dari sales representative kami, Anda bisa langsung bertanya melalui Telp atau WhatsApp untuk penawaran terbaik.